Iron and Manganese Filters
Removes iron, manganese, rust stains and metallic taste from well water with catalytic media.
- 0.5 – 100 m³/h
- Oxidation + catalytic filtration…
Free calculator
Calculate treatment need, oxidant dose and filter diameter from iron, manganese, pH and flow.
Results update instantly as you type.
Results are for preliminary sizing; the final design is based on water analysis and a site survey.
Limits are 0.2 mg/L iron and 0.05 mg/L manganese. Stoichiometric oxidant demand is ~0.64 mg/L chlorine per mg/L iron and ~1.29 per mg/L manganese (KMnO₄: 0.94 and 1.92). Catalytic filters run at 8–12 m/h; manganese needs pH above 8.
Recommended systems
Removes iron, manganese, rust stains and metallic taste from well water with catalytic media.
Multi-stage well water treatment against iron, manganese, hardness, odour, nitrate and bacteria.
Proportional and measurement-controlled dosing pumps for chlorine, antiscalant and pH chemicals.
Free site survey & water analysis
We survey your site and analyse your raw water, then present the system that fits your needs and budget in a technical report.